Accessory for ELANCIO

HYDRO, non traffic, 1969-1982

AJAX, non traffic, with square base, 1969-1982

TRI, non traffic, 1969-1982

ATLAS, non traffic and traffic, without adjustment
box

According to H Either the accessory can be buried in
the ground, Or it can be cut by section of 40 mm if the ground
is very hard

The accessory consists of 2 elements.Each element will
be laid on each side of the body of the fire hydrant and then
they will be joined together.

After assembly the accessory must be correctly
oriented. The lower part of the cover must be laid on the
corresponding shape on the accessory.

Accessory for ELANCIO

RANGE / MARK ®
FH ® ELANCIO
Accessories FIRE PROTECTION
PRODUCT FAMILY
FIRE PROTECTION
FIRE PROTECTION
Main features
Height
169
mm
Length
321
mm
Width
314
mm
Mass
0.890
kg
Reference
215586

Field of use

Restoration of the old PAM Pillar Fire Hydrant with ELANCIO cover.

HYDRO, non traffic, 1969-1982

H1 > 780 and < 940

or

H2 > 755 and < 915

To lay out the accessory (which can be cut) between the base of the cover and the ground.

For H1 > 940 or H2 > 915, an additional backfill under the accessory is necessary.

AJAX, non traffic, with square base, 1969-1982

H1 > 810 and < 970

ou

H2 > 755 and < 915

To lay out the accessory (which can be cut) between the base of the cover and the ground.

For H1 > 970 or H2 > 915, an additional backfill under the accessory is necessary.

TRI, non traffic, 1969-1982

H1 > 755 and < 915

To lay out the accessory (which can be cut) between the base of the cover and the ground.

For H1 > 915, an additional backfill under the accessory is necessary.

ATLAS, non traffic and traffic, without adjustment box

H1 > 755 and < 915

To lay out the accessory (which can be cut) between the base of the cover and the ground.

For H1 > 915, an additional backfill under the accessory is necessary.

Description

Laying

Depending on the height of the ELANCIO cover with the ground level, H dimension, it will be possible to lay an accessory between the base of the cover and the ground.

According to H Either the accessory can be buried in the ground, Or it can be cut by section of 40 mm if the ground is very hard

The accessory consists of 2 elements.Each element will be laid on each side of the body of the fire hydrant and then they will be joined together.

After assembly the accessory must be correctly oriented. The lower part of the cover must be laid on the corresponding shape on the accessory.

Solutions