Works testing
Technical solutions
Works testing
Every PAM pipe and fitting undergoes a works internal pressure test, in accordance with European and International Standards.
Socket pipe
DN | Works hydraulic test pressure DN (bar) |
---|---|
60 to 300 | 40 |
350 to 600 | 30 |
700 to 1000 | 32 |
1100 to 2000 | 25 |
Class C
Every pipe is subjected to a works hydraulic pressure test at the pressure indicated in the table above.
Standards EN 545 and ISO 2531.
Socket fitting
DN | Leaktightness test | |
---|---|---|
Hydrostatic pressure | Air pressure | |
60 to 300 | 25 bar during 10 seconds visual inspection | 1 bar during 10 seconds Checking with foaming |
350 to 600 | 16 bar during 10 seconds visual inspection | |
700 to 2000 | - |
Every fitting is subjected to an air test of at least 1 bar.
Standards EN 545 and ISO 2531.
Flanged pipes and fittings
DN | Leaktightness test |
---|---|
40 to 2000 | Air test at 1 bar Checking with foaming agent or water immersion |
Pipes are designed and individually works tested in compliance with the above criteria.
Every fitting is subject to an air test at 1 bar.
Standards EN 545 and ISO 2531.