Underground Fire Hydrant
Main features
References Upgraded design
-
References Heavy-Duty design
-
Mass
19.0
kg
Reference
214466

Material and coatings

ItemDesignationMaterial Standard version

1

Hydrant body

Ductile Iron coated with epoxy powder 250 microns

2

Cover

3

Operating cap

4

Washer

Cu

5

O-ring Ø20

EPDM

6

O-ring Ø37

EPDM

7

O-ring Ø70

EPDM

8

O-ring Ø120

EPDM

9

Piston

Ductile Iron

10

Cap

EPDM

11

Disc body

Ductile Iron

12

Pin

Stainless steel X20Cr13

13

Screw M8x40

Stainless steel A2-70

14

Nigerian bayonet outlet

Ductile iron

15

Sealing nut

CW 614 N

16

Operating stem

Stainless steel X20Cr13

17

Operating nut

CW 614 N

18

Rubberized disc

EPDM

19

Screw M12x30

Stainless steel A2-70

20

Washer

Stainless steel A2

21

Screw pin M6x8

Stainless steel A2

22

Drain valve

Hostaform

23

Drain valve washer

EPDM

24

Drain valve spring

Stainless steel X2CrNi 18-8

25

Drain valve washer

Nylon

26

Plastic cap

PE

27

Plastic cap

PE

28

Screw M12x35

Stainless steel A2-70

29

Brass ring

CW 614 N

Technical characteristics

  • Factory Test pressure: - Body: 25 bar (EN 12266 rate A – ISO 5208 rate A) - Shutter: 18 bar (EN 12266 rate A – ISO 5208 rate A)
  • Coating: fusion bonded epoxy powder in accordance with UBA, WRAS
  • Standard: BS 750 – EN 1074-6
  • Maximum service temperature: 60° C
  • Head losses in full open position: Kv = 96,4
  • Operating turns: 8
  • Operating cap: pyramidal to BS 750
  • Flanges: BS EN 1092-2 ; BS 10 ; Table D and E 3” and 3.5”, ISO PN10/16
  • Maximum allowable pressure (PFA): 16 bar
  • Nozzle type: inlet flange Da Costa/Barbados bayonet outlet
  • Size range: DN80