The euro 20 gate valve should not be outside the
hatched zone

Orientation pillar from 0 to 360°. Wrench Torx-12
mm

Close the pillar

Open one outlet

Flush the system at high flow

Check that the pillar is empty

Close the outlet
Fire hydrant C9+ Non Traffic DN100 - BS outlets
![]() |
|
Material and coating
![]() |
Item | Designation | Material | Coating |
1 | 1a -Operating cap | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Dacromet + grey Polyurethane 20 µm |
1c -Upper body | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Epoxy powder 250 µm + red Polyurethane 40 µm | |
1d-Extension tube | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Epoxy powder 250 µm + red Polyurethane 40 µm on 300 mm | |
1e -Duck foot | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Epoxy powder 250 µm | |
1b- Cover | ABS | Red polyurethane paint | |
2 | Upper and lower bush | Brass type Cu Zn 39 Pb 2EN 12164 | |
3 | Operating stem | Steel type X20 Cr 13 EN 10088-3 | |
4 | Operating nut | Brass type Cu Zn 40 Pb 2 EN 12164 | |
5 | Fixing screw | Steel type CL 8/8 | Dacromet |
6 | Operating rod | Steel type Tu 56 B | Galvanized |
7 | Valve | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Encapsulated EPDM |
8 | Outlets | Depending on models | |
10 | Screw CHC M 8 x 25 | Steel type CL 8/8 | Bichromated zinc |
Mechanical characteristics
- According to NF S 61213
- PFA 16 bars (hydraulics test: According to ISO 5208)
- Opening-closing torque bellow 80 Nm
- Maximum strength torque above 300 Nm
- Resistance to 1000 cycles opening/closing
- Number of turns to close: 13
- Nominal flow rate 60m3/h for headloss 1 m. water column
- Flow curve for PI C9+ DN100 (with headloss 1 bar:10 m. water column) according to the numbers of turns opening
![]() |
Installation
1- Surface boxes | ![]() | |
2- Gate valve Euro 20 | ||
3- S height adjustment bends | ||
4- Concrete block | ||
5- Drain orifice | ||
6- Anchorage concrete block at ground level 50 x 50 x thickness 15cm | ||
Installation DN100 | ||
Hc | H | |
1000 | 500 to 600 maxi | |
1250 |
The euro 20 gate valve should not be outside the hatched zone![]() | Orientation pillar from 0 to 360°. Wrench Torx-12 mm![]() |
Close the pillar![]() | Open one outlet![]() | Flush the system at high flow![]() | Check that the pillar is empty![]() | Close the outlet![]() |