Fire hydrant C9+ Traffic DN100 - BS outlets

Straight valve box

The EURO 20 gate valve should not be outside the
hatched zone

Orientation pillar from 0 to 360°. Wrench Torx-12
mm

Close the pillar

Open one outlet

Flush the system at high flow

Check that the pillar is empty

Close the outlet

Fire hydrant C9+ Traffic DN100 - BS outlets

RANGE / MARK ®
FH ® C9+
CHOICE OF PRODUCT
BS Outlet
PRODUCT FAMILY
FIRE PROTECTION
FIRE PROTECTION
Main features

  • Operating square cap 30x30mm
  • Bended valve box
  • Automatic drainage function
  • Outlets: 2 lateral outlets BS336 and 1 frontal outlet BS336

Material and coating

ItemDesignationMaterialCoating

1

1a -Operating cap

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Dacromet + grey Polyurethane 20 µm

1c -Upper body

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Red-brown Epoxy powder 250 µm + red Polyurethane 40 µm

1f – Lower BodyDuctile iron GS EN GJS 400-15 or 500-7 EN 1563Epoxy powder 250 µm + red Polyurethane 40 µm
1 g – Screwed boxDuctile iron GS EN GJS 400-15 or 500-7 EN 1563Epoxy powder 250 µm + red Polyurethane 40 µm

1d-Extension tube

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Blue Epoxy powder 250 µm

1e -Valve box

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Blue Epoxy powder 250 µm

1b- Cover

Polyamide P A 6

Red polyurethane paint

2

Upper and lower bush

Brass type Cu Zn 39 Pb 2EN 12164

3

Operating stem

Steel type X20 Cr 13 EN 10088-3

4

Operating nut

Brass type Cu Zn 40 Pb 2 EN 12164

5

Fixing screw

Steel type CL 8/8

Bichromated zinc

6

Operating rod

Steel type Tu 56 B NF EN 10240

Galvanized

7

Valve

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Encapsulated EPDM

8

Outlets

Depending on models

9Operating shaftX20 Cr 13 EN 10088-1

10

Pin

X20 Cr 13 EN 10088-1
11Operating spindle(OS) Forged steel C35 - NF EN 10083-125 microns black cataphoresis
12Bolts and nutsSteel type CL 8/8Bichromated zinc
13Breakable traffic clamping shimDuctile iron250 microns fusion bonded blue epoxy + red polyurethane

Mechanical characteristics

  • According to NF S 61213
  • PFA 16 bars (hydraulics test: According to ISO 5208)
  • Opening-closing torque bellow 80 Nm
  • Maximum strength torque above 300 Nm
  • Resistance to 1000 cycles opening/closing
  • Number of turns to close: 13
  • Nominal flow rate 60m3/h for headloss 1 m. water column
  • Flow curve for PI C9+ DN100 (with headloss 1 bar:10 m. water column) according to the numbers of turns opening

Installation

1- Surface boxes

2- Gate valve Euro 20

3- S height adjustment bends

4- Concrete block

5- Drain orifice

6- Anchorage concrete block at ground level 50 x 50 x thickness 15cm

Installation DN100

Hc

H

1000

500 to 600 maxi

1250

The EURO 20 gate valve should not be outside the hatched zone

Orientation pillar from 0 to 360°. Wrench Torx-12 mm

Close the pillar

Open one outlet

Flush the system at high flow

Check that the pillar is empty

Close the outlet