Fire hydrant C9+ Traffic DN100 - NFPA outlets

NFPA outlet

Fire hydrant C9+ Traffic DN100 - NFPA outlets

RANGE / MARK ®
FH ® C9+
CHOICE OF PRODUCT
NFPA Outlet
PRODUCT FAMILY
FIRE PROTECTION
FIRE PROTECTION
Main features
DN
100
mm
Version
Bended box
Outlets
2xNFPA 194 2"½ + 1xNFPA 194 4"½-4"
P=HC
1006
mm
H
2015
mm
H1
643
mm
H2
538
mm
H3
1175
mm
E
152
mm
S
100 x 90
mm
Mass
80
kg
Reference
184814

  • Operating square cap 30x30mm
  • Bended valve box or straight valve box
  • Automatic drainage function
  • Outlets: 2 NFPA lateral outlets and 1 NFPA frontal outlet

Material and coating

ItemDesignationMaterialCoating

1

1a -Operating cap

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Dacromet + grey Polyurethane 20 µm

1c -Upper body

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Red-brown Epoxy powder 250 µm + red Polyurethane 40 µm

1f – Lower BodyDuctile iron GS EN GJS 400-15 or 500-7 EN 1563Epoxy powder 250 µm + red Polyurethane 40 µm
1 g – Screwed boxDuctile iron GS EN GJS 400-15 or 500-7 EN 1563Epoxy powder 250 µm + red Polyurethane 40 µm

1d-Extension tube

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Blue Epoxy powder 250 µm

1e -Valve box

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Blue Epoxy powder 250 µm

1b- Cover

Polyamide P A 6

Red polyurethane paint

2

Upper and lower bush

Brass type Cu Zn 39 Pb 2EN 12164

3

Operating stem

Steel type X20 Cr 13 EN 10088-3

4

Operating nut

Brass type Cu Zn 40 Pb 2 EN 12164

5

Fixing screw

Steel type CL 8/8

Bichromated zinc

6

Operating rod

Steel type Tu 56 B NF EN 10240

Galvanized

7

Valve

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Encapsulated EPDM

8

Outlets

Depending on models

9Operating shaftX20 Cr 13 EN 10088-1

10

Pin

X20 Cr 13 EN 10088-1
11Operating spindle(OS) Forged steel C35 - NF EN 10083-125 microns black cataphoresis
12Bolts and nutsSteel type CL 8/8Bichromated zinc
13Breakable traffic clamping shimDuctile iron250 microns fusion bonded blue epoxy + red polyurethane

Solutions