Suction Pillar Hydrant in load C9+ Non Traffic
A good choice on a long term period SG PAM Pillar Hydrants are designed to last in time without particular intervention; their functionalities are kept even after many years of use. The product was qualified in our PAM Laboratory accredited COFRAC. The product offers higher performances compared to the requirements of the standards: • a number of opening and closing higher than the 1,000 necessary cycles; • a resistance of the envelope to the pressure higher than 25 bars; • easily manoeuvrable with operating torques lower than 80 Nm. | ![]() |
Bended valve box - Depth of cover 1m - Outlet DN100
Material and coating
![]() |
Item | Designation | Material |
71 | Counter-flange | Ductile iron EN GJS 400-15 or 500-7 EN 1563 |
70 | Screwed flange | Ductile iron EN GJS 400-15 or 500-7 EN 1563 |
65 | Joint DN65 | Polyurethane |
64 | Joint DN100 | Polyurethane |
61 | Plug DN65 | Aluminium |
60 | Kit outlet + symmetrical plugs DN100 | Aluminium AS7G Y33 NF EN 1706 |
32 | Operating cap | Ductile iron EN GJS 400-15 or 500-7 EN 1563 |
31 | Screw CHc M8x25 | Steel Cl 8/8 zinc coated Bichromated |
30 | Foam-rubber joint 42x22 | EPDM |
29 | Number plate | Aluminium |
28 | Cover of marking | ASA |
27 | Thrust washer 39x26 | Cu Sn 7 Pb 6 Zn 4 NF EN 1982 |
26 | Friction ring 36x25.5 | PA 6-6 |
25 | Joint R16 | EPDM NF EN 681-1 |
24 | Joint R29 | EPDM NF EN 681-1 |
23 | Screwed stage M44x2.5 | Cu Zn 38 Pb 2 NF EN 12420 |
22 | Body C9 Plus | Ductile iron EN GJS 400-15 or 500-7 EN 1563 |
21 | O’ring 115x8 | Elastomer CL 70 (alimentary) |
18 | Washer Z12 | Steel Cl 6/6 zinc coated Bichromated |
17 | Screw A T-basse Torx M12x50 | Steel Cl 8/8 zinc coated Bichromated |
12 | Adjusting screw HM 8x8 | Stainless steel A2-70 ISO 3506 |
10 | Operating nut | Cu Zn 40 NF EN 12420 |
9 | Operating screw | X 20 Cr 13 NF EN 10088-3 |
8 | Operating rod 1445 | Steel TU 56-8 NF EN 10240 |
7 | Tube allonge 1120 | Ductile iron NF EN 545 |
6 | Joint | Polyurethane |
5 | Pin diam 8x65 | X 20 Cr 13 NF EN 10088-3 |
4 | Moulded valve | Ductile iron NF EN 1563 + EPDM |
3 | Jacket | Cu Sn 6 Zn 4 Pb 2 EN 1982 or Cu Zn 40 |
2 | Half flange DN100 | Ductile iron EN GJS 400-15 or 500-7 EN 1563 |
1 | Bended valve box | Ductile iron EN GJS 400-15 or 500-7 EN 1563 |
Final coating:
Epoxy + blue polyurethane (RAL 5005) thickness 250 microns mini inside and outside to have an excellent resistance against corrosion. A complementary coating on the upper part offers a good resistance to climatic factors: sun, moon, bad weather, etc…
Alimentarity
The product is in conformity with the French regulation.
It obtained the Sanitary Conformity certificate (ACS).
Technical characteristics
Pillar hydrant operating:
- Square: 30x30 mm
- Closing direction: clockwise
- Number of revolutions: 13
- Kv coefficient: 160
- Diameter of the outlet: Ø100 symmetric
- Connection flange: drilling ISO PN10/16
- Allowable operating pressure (PFA): 16 bars
- Factory test pressure: Body: 25 bars Plug: 18 bars
Hydraulic performances
Flow of the pillar hydrant C9 + non traffic DN100 according to the number of operating revolutions and creating a pressure loss of 1 bar with full opening.
Reliable and perennial closing system
The closing system used with the products of the fire network was designed to guarantee the maximum security.
Easy draining without maintenance
Automatic draining.
The fire hydrant equipped with a plug must be completely empty after use to avoid the risks of freezing in winter. SG PAM developed a completely automatic system of draining made up of a simple opening integrated in the ductile iron of the valve box.
Single design without component:
- No maintenance
- Perennial operation
- No spare parts
Fire hydrant in closed position (drawing 1)
• The valve releases the opening of draining and water is evacuated gravitationally.
Fire hydrant in opened position (drawing 2)
• The valve closes the draining from the beginning of the opening to the total opening. There is no loss of water during the opening operation.
Progressive and durable valve
Valve made up of two ductile iron parts covered with EPDM. This technology enables a perennial tightness.
During the closing operation, the two parts approach by compressing the EPDM to have a durable tightness.
The closing system has been studied so that the flow is established in a progressive way at the opening and closing of the fire hydrant to avoid any risks of water hammer (sinusoidal tightness line).
Closing system with right geometry to avoid its blocking by possible foreign elements contained in water (stones for example) which could involve a tightness defect.
A great simplicity of installation and use
Earthwork is not necessary and the fire hydrants are directional on 360°.
The smooth barrel without bolt avoids the problems of corrosion of the fire hydrant, and is integrated directly in the ground, which makes it possible to simplify works of completion or landscape installation surrounding.