Every PAM pipe and fitting undergoes a works internal pressure test, in accordance with European and International Standards.

Socket pipes
DN Works hydraulic test pressure
DN (bar)
60 to 300 40
350 to 600 30
700 to 1000 32
1100 to 2000 25

 

Class C

Every pipe is subjected to a works hydraulic pressure test at the pressure indicated in the table above.
Standards EN 545 and ISO 2531.

 

Socket fittings
DN Leaktightness test
Hydrostatic pressure Air pressure
60 to 300 25 bar during 10 seconds
visual inspection
1 bar during 10 seconds
Checking with foaming
350 to 600 16 bar during 10 seconds
visual inspection
700 to 2000 -


Every fitting is subjected to an air test of at least 1 bar.
Standards EN 545 and ISO 2531.

Flanged pipes and fittings
DN Leaktightness test
40 to 2000 Air test at 1 bar Checking with foaming agent or water immersion


Pipes are designed and individually works tested in compliance with the above criteria.
Every fitting is subject to an air test at 1 bar.
Standards EN 545 and ISO 2531.