Air valve type VENTEX SR
Air_valve_type_VENTEX_SR
Air valve type VENTEX SR
Air_valve_type_VENTEX_SR

Air valve type VENTEX SR (without isolating system) - Reinforced
version

Product family
Pipeline protection

The Ventex SR air valves are without shutter gasket.

The air valves protect the main:

The device evacuates great air amounts during the filling of the main:

allows the inlet of great air amounts (in order to avoid a vacuum effect) during the emptying of the main

evacuates small air amounts that are accumulated in the high points of the main during normal working conditions

The Ventex SR air valves are without shutter gasket. They are less bulky and easier to handle. They therefore do not include isolating system.

The air valves are in conformance with EN 1074-4 and have a certificate of sanitary conformity.

Warning: in order to allow the maintenance, the air valves must be installed with a concentric butterfly valve Lug type or an isolating valve Euro 20 type between the network and the air valve.

Range

Air Valves Type VENTEX SR exist in a range stretching from DN50 to 200, for pressure PFA10, PFA16 and PFA25.

,

DN Air valve E F H h1 a s
mm mm mm mm mm mm mm
50-65 390 200 258 165 20 15.3
80-100 467 244 300 215 20 15,3
150 656 405 492 285 24 18,5
200 737 448 580 330 29 20,7

,,

Nozzle diameter
Working pressure (bar) 10 16 25
Diameter (mm) for DN Air valve 65 2.2 1.7 1.4
Diameter (mm) for DN Air valve 80 to 200 3 2.4 1.9

,

Connecting flange: 65 type double air valve is fitted with an ISO PN10-16 or ISO PN25 DN60 rotatable flange

Other flanges available:

ISO PN10-16 or ISO PN25 rotatable DN65 flange

DN50 fixed flange.

Technical design

Air_valve_type_VENTEX_SR
50 10 25 *
50 16 25 252926
50 25 25 252931
60 10 25 *
60 16 25 *
60 25 25 *
65 10 27 252936
65 16 27 252923
65 25 27 *
80 10 40 252935
80 16 40 252922
80 25 40 252930
100 10 40 252934
100 16 40 252921
100 25 40 252929
150 10 115 252933
150 16 115 252890
150 25 115 252928
200 10 186 252932
200 16 186 252887
200 25 186 252927

Features

Allows during the emptying of the main with a speed 1m/s

Main DN ≤ 250 DN300-600 DN700-900 DN1000-1200 DN1200-1800
Air Valve DN50, 60, 65 DN80,100 DN150 DN200 2 DN200

This Ventex choice allows, in case of break main, to limit maximal pressure drop 0,3 Bar for a flow rate with a part full gravity pipeline on a given slope: See paragraph Performances.

Material and coating

Item Designation Material
10, 11 Body, Bonnet FGS 400/15 ou 500-7 coated epoxy 300 µ mini acc. EN 1563
2-1, 2-2, 2-3 Body-bonnet: bolts and washers Stainless steel A4
3 Body-bonnet gasket EPDM Rubber acc. EN681-1
4-1 Large orifice seat NBR rubber encapsulated SG 400/15 ductile iron acc. EN 1563
4-2+4-3+4-4 Seat: bolts and washers Stainless steel A4
5 Nozzle and nozzle control Cu Al 10 Ni3 Fe2 alu-bronze type
6-1 and 6-2 Float balls EPDM rubber encapsulated Core in steel DC03 or DC04 to EN 10130 and DD11 or DD13 to EN 10111 steel type
Ventex_SR-nom

Performances

Water flow in case of break

Examples of Use: for a main DN600 laid inclined 4mm/m flow water around 1800 m3/h , flow which will not create a depression higher than 0,3b according to graph air flow large orifice below

VENTEX_performances

Air flow large orifice

Air Flow output by large orifice in m3/h (with the pressure of main: air flow = water flow) - Air Flow input by large orifice in m3/h (with the pressure of main: air flow = water flow)

Nozzle air flow

Constant Flow from 1 bar (10MCE) 

PFA in Bar 10 16 25
DN in mm 50-65 80-200 50-65 80-200 50-65 80-200
Ø nozzle in mm 2,2 3 1,7 2,4 1,4 1,9
Flow in m3/h 2,7 5 1,6 3,2 1,1 2

Hydraulic

Small and large Float balls: External leakage

No leakage in low pressure from 0,3 bars

VENTEX_debit

Marking

The marking of the valves manufactured by Saint-Gobain refers to the EN 1074-2 and EN 19 international standards.

Markings are either integral markings, cast in the body, or markings made on plates, securely fixed to the body, in accordance with the EN 19 standard specifications.

EN 19 Specifications Saint-Gobain valves process
Table 1 – Valve markings Requirements
1 DN

EN 19 § 4.2.1

Mandatory markings

Shall be integral markings or on a marking plate

Integral
2 PN Integral
3 Material Integral
4 Manufacturer's name or trademark Plate
11 Reference to Standard

EN 19 § 4.3

Supplementary markings

Items 7 to 21 in Table 1 are optional

Plate
12 Melt identification Integral
16 Quality test Printed on body
18 Manufacturing date Plate
21 Closing direction Plate + sticker on body
VENTEX_marquage
VENTEX_marquage
VENTEX_marquage

Installation

Mounting with gate valve (Concentric LUG Butterfly valve or Euro 20 NG type 23 with or without reducing flange): only for a repairing without water cut: operating system or shutter gasket insert gate valve

  1. Standard Mounting with Concentric LUG Butterfly Valve
  2. Mounting with EURO 20 NG type 23
  3. Mounting with two air valves DN200: for pipes DN1400 up to DN1800: to realize according to sketch on a tee 3 equal socket and a special Blank flange

Related products :

  • Concentric LUG butterfly valve
  • Gate valve Type Euro 23 for PFA10, 16 - Gate valve Type RVOM for PFA25
Ventex_SR_installation
Ventex_SR_installation
VENTEX_installation
4.