Automatic flow limiting valve with remote electric control - E3114-01 - E4114-01
AUTOMATIC CONTROL VALVES

Automatic flow limiting valve with remote electric control - E3114-01 / E4114-01

Product family
Pipeline protection

The E3114-01 / E4114-01 automatic valve maintains the flow rate within a set maximum limit, regardless of pressure fluctuations.

If the flow rate remains below the value required the valve remains fully open.

Thanks to a solenoid valve, the valve can also be opened and closed remotely.

The pilot is connected to a flanged orifice to be installed on the pipeline.


Equipped with a visual position indicator in the standard version, the valve is made of stainless steel and ductile iron coated with epoxy paint using a fluidized bed technique.

Technical design

E3114-01 80 10 16 31 E34A8016P01
E3114-01 100 10 16 37 E34B1016P01
E3114-01 125 10 16 57 E34B1216P01
E4114-01 150 10 16 97 E44B1516P01
E3114-01 150 10 16 64 E34B1516P01
E3114-01 200 10 110 E34B2010P01
E3114-01 200 16 110 E34B2016P01
E3114-01 250 10 188 E34B2510P01
E3114-01 250 16 188 E34B2516P01
E3114-01 300 10 305 E34B3010P01
E3114-01 300 16 305 E34B3016P01
E3114-01 400 10 516 E34B4010P01
E3114-01 400 16 516 E34B4016P01
E3114-01 500 10 862 E34B5010P01
E3114-01 500 16 862 E34B5016P01
E3114-01 600 10 1002 E34B6010P01
E3114-01 600 16 1002 E34B6016P01
E4114-01 40/50 10 16 25 E44A5016P01
E4114-01 65 10 16 27 E44A6516P01
E4114-01 80 10 16 31 E44A8016P01
E4114-01 100 10 16 49 E44B1016P01
E4114-01 200 10 154 E44B2010P01
E4114-01 200 16 154 E44B2016P01
E4114-01 250 10 265 E44B2510P01
E4114-01 250 16 265 E44B2516P01
E4114-01 300 10 441 E44B3010P01
E4114-01 300 16 441 E44B3016P01
E4114-01 400 10 784 E44B4010P01
E4114-01 400 16 784 E44B4016P01
E4114-01 600 10 2250 E44B6010P01
E4114-01 600 16 2250 E44B6016P01

Features

Applications

  • Downstream of pumps to prevent overloads and damages related to cavitation with remote control in case of emergency.
  • On the supply lines of the tanks to limit the range, even in combination with an electronic floating probe.
  • In the distribution networks of residential neighborhoods and industrialists to limit the flow in rush hour.

Accessories

  • The position indicator with 4-20 mA output.
  • The open-close indicator.
  • Manometers.
  • Self-cleaning high capacity filter.

Notes to the designer

  • Modulation systems ensure accurate regulation even with low flow rates and high pressure differentials.
  • For best operation, it is recommended to leave a straight section of pipe 5 diameters long between the valve and the calibrated flange, and another segment, 3 diameters long, downstream of the latter (image on the next page).

Optional configurations

  • Flow control valve with solenoid control and anti-backflow system.
  • Flow regulation with solenoid control and high sensitivity pilot.

Operating conditions

  • Fluid: treated water.
  • Minimum pressure: 1,2 bar.
  • Maximum pressure: 16 bar.
  • Maximum temperature: 70 °C.

Pilot flow regulation field

  • The flanged orifice is sized according to the maximum design flow rate. Variations from the setting value are possible in accordance with the flow rate table supplied with the valve.

Solenoid valve data

  • Voltage: 24V DC, 24V/50Hz, 230V/50Hz. Other voltage on request.
  • Electrical consumption: inrush AC (VA) 24, hold AC (VA) 17 (8 W), DC hot/cold coil 8/9 W.

How it works

The valve is controlled by an adjustable two-way pilot (5) for flow control, which receives the pressure downstream of the flanged orifice (13) in its cap.

When the flow rate exceeds the maximum value, the pilot (5) modulates the flow passing through it by directing the upstream pressure into the valve chamber (10), so as to lower the shutter (11) towards the seat (12) to reduce the flow.

When the flow rate remains below the established limit, the pressure at the flanged orifice (13) is less than the force of the pilot spring, so that the pilot remains completely open, as does the main valve.

Furthermore, a solenoid (16), in combination with an auxiliary two-way valve (15), by regulating the flow of the circuit, closes or opens the main valve depending on the impulses received.

The flow into and out of the main chamber (10) is controlled by the exclusive regulation unit (4), necessary to ensure stability and make the opening and closing speeds of the valve independent of each other.

Automatic flow limiting valve with remote electric control - E3114-01 - E4114-01-functioning

Installation diagram

The valve must be connected to a control unit (10) or other electronic control devices.

The calibrated flange (8), with an orifice sized according to the project requirements, is connected to the pilot (9).

Shut-off devices (1, 2) and bypasses, with direct-acting valves (4), are recommended to allow maintenance.

The insertion of combined anti-water hammer vents FBA (6, 7) and a DRV-S relief valve (5) is also recommended.

Automatic flow limiting valve with remote electric control - E3114-01 - E4114-01-installation