Booster Pump E3113-06 - E4113-06
AUTOMATIC CONTROL VALVES

Booster Pump E3113-06 / E4113-06

Product family
Pipeline protection

The E3113-06/E4113-06 valve is a globe pattern hydraulically operated automatic control valve, active check valve, that isolates the pump from the system during pump starting and stopping to prevent and avoid surges and water hammer events.

The valve opens and closes in response to signals applied to the solenoid on the circuit where a needle valve will adjust the response time for an accurate and smooth regulation.

Equipped with a limit switch activated by the position indicator’s movement, made in ductile cast iron and stainless steel, the valve is designed to reduced head loss, throttling noise and cavitation damage.


Flange drilling according to EN 1092/2, different on request.


Certification and testing according to EN 1074.

Technical design

E3113-06 80 10 16 25 E33A8016P06
E3113-06 100 10 16 32 E33B1016P06
E3113-06 125 10 16 47 E33B1216P06
E3113-06 150 10 16 54 E33B1516P06
E3113-06 200 10 97 E33B2010P06
E3113-06 200 16 97 E33B2016P06
E3113-06 250 10 172 E33B2510P06
E3113-06 250 16 172 E33B2516P06
E3113-06 300 10 287 E33B3010P06
E3113-06 300 16 287 E33B3016P06
E3113-06 400 10 496 E33B4010P06
E3113-06 400 16 496 E33B4016P06
E3113-06 500 10 862 E33B5010P06
E3113-06 500 16 862 E33B5016P06
E3113-06 600 10 1002 E33B6010P06
E3113-06 600 16 1002 E33B6016P06
E4113-06 40/50 10 16 19 E43A5016P06
E4113-06 65 10 16 20 E43A6516P06
E4113-06 80 10 16 25 E43A8016P06
E4113-06 100 10 16 39 E43B1016P06
E4113-06 150 10 16 84 E43B1516P06
E4113-06 200 10 138 E43B2010P06
E4113-06 200 16 138 E43B2016P06
E4113-06 250 10 248 E43B2510P06
E4113-06 250 16 248 E43B2516P06
E4113-06 300 10 420 E43B3010P06
E4113-06 300 16 420 E43B3016P06
E4113-06 400 10 784 E43B4010P06
E4113-06 400 16 784 E43B4016P06
E4113-06 600 10 2250 E43B6010P06
E4113-06 600 16 2250 E43B6016P06

Features

Applications

  • At the pumps to enable start and stop cycles avoiding surges and water hammer.
  • To prevent water hammer during pump switching in batteries and parallel operation.
  • To ensure an accurate and surge free check prevention system.

Accessories

  • Manometers.
  • Self-cleaning high capacity filter.

Directions for use

  • Anti-cavitation low flow stability plugs are recommended to provide an accurate regulation in case of low flow conditions.
  • Recommended flow rate and operating conditions on the series engineering.
  • The duration of impulses sent to the solenoid is important and changes with valve size and operating pressure.

Optional configurations

  • Pressure reducing valve for booster pumps.
  • Pressure sustaining valve for booster pumps.
  • Flow control valve for booster pumps.

Operating conditions

  • Fluid: treated water.
  • Minimum pressure: 0,7 bar.
  • Maximum pressure: 16 bar.
  • Recommended working pressure: 6 bar. Higher on request.
  • Maximum temperature: 70 °C.

Solenoid valve data

  • Voltage: 24 V DC, 24 V/50 Hz, 230 V/50 Hz. Other voltage on request.
  • Consumption electrical: inrush AC (VA) 24, hold AC (VA) 17 (8 W), DC hot/ cold coil 8/9 W.

How it works

When pumps are turned off the valve (9) is closed and the solenoid (13) is de-energized.

When the pump starts, the solenoid (13) is energized and the control chamber (10) is put in communication with the downstream pressure thanks to the hydraulic accelerator (7), thus pushing the obturator (11) upwards to generate a gradual increase of the flow rate.

The needle valve (3) ensures the regulation of the opening and closing speed, to avoid sudden variations in pressure.

When shut down is required, the pump is kept running while the solenoid (13) is de-energized diverting, through the flow accelerator (7), the upstream pressure towards the control chamber (10) with gradual closing of the obturator (11) onto the seat (12).

Once the indication rod (15) has reached a pre-determined position (adjustable, usually the 20% of the valve stroke), the limit switch (6) will send a signal for the pump to close. In case of power failure, the backflow through the main valve (9) is prevented thanks to the check valve (8) allowing the downstream pressure back to the control chamber (10) minimizing surges.

Booster Pump E3113-06 - E4113-06-functioning

Installation diagram

The picture below shows the recommended installation layout of E3113-06 (1) as an effective surge prevention system and protection device for water pumping stations, in combination with pressure relief valves model E3116-10 (2) or surge anticipating E3116-52 valve.

Anti-slam combination air valves are recommended upstream (3) and downstream of the booster pump control as well as sectioning devices and bypass required for the proper maintenance.

Booster Pump E3113-06 - E4113-06-installation

Documents