Excess Flow rate Cut-off - E3117-00 - E4117-00
AUTOMATIC CONTROL VALVES

Excess Flow rate Cut-off - E3117-00 / E4117-00

Product family
Pipeline protection

The automatic valve is equipped with a highly sensitive pilot that, when the flow rate exceeds a set (adjustable) value, directs the upstream pressure into the valve control chamber causing it to close.

Reopening must be done manually.

If the flow rate remains below the set value, the valve remains fully open, with minimal pressure drops. Equipped with a visual position indicator in the standard version and made entirely of stainless steel and ductile iron coated with epoxy paint using a fluidized bed technique, the valve reduces pressure drops, vibrations and damage related to cavitation.


Flange drilling according to EN 1092/2, different on request.


Certification and testing according to EN 1074.

Technical design

E3117-00 80 10 16 28 E37A8016P00
E3117-00 100 10 16 35 E37B1016P00
E3117-00 125 10 16 51 E37B1216P00
E3117-00 150 10 16 58 E37B1516P00
E3117-00 200 10 100 E37B2010P00
E3117-00 200 16 100 E37B2016P00
E3117-00 250 10 174 E37B2510P00
E3117-00 250 16 174 E37B2516P00
E3117-00 300 10 290 E37B3010P00
E3117-00 300 16 290 E37B3016P00
E3117-00 400 10 499 E37B4010P00
E3117-00 400 16 499 E37B4016P00
E3117-00 500 10 862 E37B5010P00
E3117-00 500 16 862 E37B5016P00
E3117-00 600 10 1002 E37B6010P00
E3117-00 600 16 1002 E37B6016P00
E4117-00 40/50 10 16 22 E47A5016P00
E4117-00 65 10 16 23 E47A6516P00
E4117-00 80 10 16 28 E47A8016P00
E4117-00 100 10 16 42 E47B1016P00
E4117-00 150 10 16 86 E47B1516P00
E4117-00 200 10 140 E47B2010P00
E4117-00 200 16 140 E47B2016P00
E4117-00 250 10 250 E47B2510P00
E4117-00 250 16 250 E47B2516P00
E4117-00 300 10 423 E47B3010P00
E4117-00 300 16 423 E47B3016P00
E4117-00 400 10 786 E47B4010P00
E4117-00 400 16 786 E47B4016P00
E4117-00 600 10 2252 E47B6010P00
E4117-00 600 16 2252 E47B6016P00

Features

Applications

  • In gravity pipelines to prevent depressurization of the system in the event of pump failure or pipe breakage.
  • At the outlet of tanks and piezometric towers to interrupt the flow in the event of pump blockage and prevent the level from falling below a minimum value.
  • In pipelines and distribution networks to interrupt the flow in the event of extreme events such as earthquakes.

Accessories

  • Position indicator with 4-20 mA output.
  • Opening/closing indicator.
  • Manometers.
  • Self-cleaning high capacity filter.

Directions for use

  • Inlet and outlet pressure, flow rate and application are required for cavitation sizing and analysis.
  • It is recommended to leave a section of pipe 3 diameters long upstream and downstream of the valve.

Optional configurations

  • Excess flow shut-off valve with anti-backflow system.
  • Excess flow shut-off valve with solenoid control valve.

Operating conditions

  • Fluid: treated water.
  • Minimum pressure: 1,5 bar.
  • Maximum pressure: 16 bar.
  • Recommended operating pressure: 16 bar. Higher on request.
  • Maximum temperature: 70 °C.

Flow pilot adjustment range

  • The pilot is set to the required flow rate value . It is possible to vary the adjustment based on the table supplied with the valve.

How it works

The hydraulic valve is controlled by an adjustable high sensitivity two-way pilot (5), which senses the pressure drop across the valve as a function of the flow rate.

When the flow rate exceeds the maximum value established,

The differential of pressure increases and the pilot (5) opens. The pressure in the valve chamber (10) then reaches the level of the upstream one, with consequent closure of the shutter (11) on the site Of estate (12).

If there flow rate stay to the of below the calibration value the valve remains completely open.

Once the valve is closed it is necessary to reopen it manually, discharging water out of the circuit by means of the ball valve 13.


The flow into and out of the main chamber (10) and checked from the valve to pin (3), while a filter (4) prevents the entrance of debris and dirt in the circuit.

Excess Flow rate Cut-off - E3117-00 - E4117-00-functioning

Installation diagram

The operation of the hydraulic valve, in certain conditions, can cause phenomena of uneven motion with pressure changes, for which it is necessary to insert rapid relief valves (5) upstream.

The installation diagram also includes support valves (4) on the bypass for maintenance, as well as anti-water hammer vents (6, 7) to allow degassing during operation and the entry and exit of air during emptying and filling of the pipeline.

Excess Flow rate Cut-off - E3117-00 - E4117-00-installation