EURO FH2
FH2 Underground Fire Hydrant DN80 BS750 - Type Loose Stopper
Technical design
Technical design
| 80 | Standard design | 11.4 | 230709 |
Features
Field of use
Fire hydrants pillar or underground type are designed, according to applicable standards and regulations, for exclusive use of fire protection and using drinking water or raw water network.
They must be handled and used in strict compliance with the recommendations and best practice by personnel trained with these recommendations.
These devices must be inspected periodically (as required by regulations or recommended instructions) to verify and maintain their proper and safe operation.
Material and coatings
| Item | Designation | Standards | Material Standard Version | Material Upgraded Version | Material Heavy-duty Version |
|---|---|---|---|---|---|
| 1 | Hydrant body | BS EN 1563 |
Ductile Iron coated with epoxy powder 250 microns |
Ductile Iron coated with epoxy powder 300 microns | |
| 2 | Hydrant bonnet | BS EN 1563 |
Ductile Iron coated with epoxy powder 250 microns |
Ductile Iron coated with epoxy powder 300 microns | |
| 3 | Operating cap | BS EN 1563 |
Ductile Iron coated with epoxy powder 250 microns |
Ductile Iron coated with epoxy powder 300 microns | |
| 4 | Limiter | WARAS listed | Dupont Zytel 70G30 HSL NC010 | ||
| 5 | Outlet nozzle | BS EN 10088-3 | Stainless steel GX20Cr14 | Stainless steel G X5CrNiMo19-11-2 EN10283 (1.4408) | |
| 6 | Cap | HDPE | |||
| 7 | Rubberized disc |
BS EN 1563 - BS EN 681-1 |
Ductile Iron / EPDM | ||
| 8 | Operating nut | BS 12164 | CW 614 N | Bronze LG2 | |
| 9 | Operating stem | BS EN 10088 - 3 | Stainless steel X20Cr13 | Stainless steel X2CrNiMo 17-12 | |
| 10 | Limiter | BS 12164 | CW 614 N | Bronze LG2 | |
| 11 | Wiper ring | BS EN 681-1 | EPDM | ||
| 12 | Drain Valves | WARAS listed | Dupont Zytel 70G30 HSL NC010 | ||
| 13 | Washer | BS 4320 | B NAYLON | ||
| 14 | Spring | EN 10270 - 3 | Stainless steel X2CrNi 18-8 | ||
| 15 | Washer | BS EN 681-1 | EPDM | ||
| 16 | “O” Ring Ø75XØ5 | BS EN 681-1 | EPDM | ||
| 17 | “O” Ring Ø105XØ5 | BS EN 681-1 | EPDM | ||
| 18 | “O” Ring Ø26XØ3 | BS EN 681-1 | EPDM | ||
| 19 | “O” Ring Ø23XØ2,5 | BS EN 681-1 | EPDM | ||
| 20 | Screw M8x35 | ISO 4017 | Stainless steel A2 - 70 | Stainless steel A4 - 80 | |
| 21 | Screw M12x40 | ISO 4017 | Stainless steel A2 - 70 | Stainless steel A4 - 80 | |
| 22 | Screw M12x45 | ISO 4017 | Stainless steel A2 - 70 | Stainless steel A4 - 80 | |
| 23 | Washer A12 | ISO 7089 | Stainless steel A2 | Stainless steel A4 | |
| 24 | Nut M12 | ISO 4032 | Stainless steel A2 | Stainless steel A4 | |
| 25 | Screw M8x16 | ISO 4762 | Stainless steel A2 - 70 | Stainless steel A4 - 80 | |
| 26 | Sealing Nut | BS 12164 | CW 614 N | Bronze LG2 | |
| 28 | Washer A24 | ISO 7089 | Stainless steel A2 | Stainless steel A4 | |
Technical characteristics
- Factory Test pressure:
- Body: 25 bar (EN 12266 rate A – ISO 5208 rate A)
- Shutter: 18 bar (EN 12266 rate A – ISO 5208 rate A)
- Coating: fusion bonded epoxy powder in accordance with UBA, WRAS
- Standard: BS 750 – EN 1074-6
- Maximum service temperature: 60° C
- Head losses in full open position: Kv = 96,4
- Operating turns: 8
- Operating cap: pyramidal to BS 750
- Flanges: BS EN 1092-2 ; BS 10 ; Table D and E 3” and 3.5”, ISO PN10/16
- Maximum allowable pressure (PFA): 16 bar
- Nozzle type: 2 ½ inches London round thread to BS 750
- Size range: DN80
Hydraulic characteristics
Documents
Documents