Flow Rate Automatic Control Valve - E3114-00 - E4114-00
AUTOMATIC CONTROL VALVES

Flow Rate Automatic Control Valve - E3114-00 / E4114-00

Product family
Pipeline protection

It is a globe pattern hydraulically operated automatic control valve that limits the flow to a pre-set value, regardless of pressure variations.

In case of flow rate lower than the required set point the valve will be fully opened.

The valve is supplied with an orifice plate assembly, needed for the proper functioning and connected to the pilot.


Normally equipped with visual position indicator and entirely made in ductile cast iron with FBT (fluid bed technology) epoxy coating and stainless steel, the valve is designed to reduce head loss, throttling noise and cavitation damage.

Technical design

E3114-00 80 10 16 30 E34A8016P00
E3114-00 100 10 16 37 E34B1016P00
E3114-00 125 10 16 56 E34B1216P00
E3114-00 150 10 16 63 E34B1516P00
E3114-00 200 10 109 E34B2010P00
E3114-00 200 16 109 E34B2016P00
E3114-00 250 10 187 E34B2510P00
E3114-00 250 16 187 E34B2516P00
E3114-00 300 10 304 E34B3010P00
E3114-00 300 16 304 E34B3016P00
E3114-00 400 10 515 E34B4010P00
E3114-00 400 16 515 E34B4016P00
E3114-00 500 10 862 E34B5010P00
E3114-00 500 16 862 E34B5016P00
E3114-00 600 10 1002 E34B6010P00
E3114-00 600 16 1002 E34B6016P00
E4114-00 40/50 10 16 24 E44A5016P00
E4114-00 65 10 16 26 E44A6516P00
E4114-00 80 10 16 31 E44A8016P00
E4114-00 100 10 16 48 E44B1016P00
E4114-00 150 10 16 96 E44B1516P00
E4114-00 200 10 153 E44B2010P00
E4114-00 200 16 153 E44B2016P00
E4114-00 250 10 264 E44B2510P00
E4114-00 250 16 264 E44B2516P00
E4114-00 300 10 440 E44B3010P00
E4114-00 300 16 440 E44B3016P00
E4114-00 400 10 784 E44B4010P00
E4114-00 400 16 784 E44B4016P00
E4114-00 600 10 2250 E44B6010P00
E4114-00 600 16 2250 E44B6016P00

Features

Applications

  • Downstream of pumps to prevent overload and for cavitation protection.
  • On the inlet supply lines of tanks to prevent excessive flow.
  • In distribution networks and on the supply lines of residential and industrial districts to limit the flow during peak hours.
  • In filtration systems to prevent excessive flow avoiding damages and malfunctioning.

Accessories

  • Linear position transmitter with 4-20 mA output Mod. CSPL.
  • On-off position transmitter Mod. CSPO.
  • Pressure measurement kit.
  • Self-flushing and high capacity filter.

Note to the engineer

  • Inlet and outlet pressure, flow rate are required for the proper sizing.
  • Anti-cavitation low flow stability plugs are recommended to provide an accurate regulation in case of low flow conditions.
  • For the best accuracy leave 5 DN between the valve and the orifice plate and 3 DN downstream of it (picture in the next page).

Additional features

  • E3114-00-FR flow rate control valve with back-flow prevention.
  • E3114-00-H flow rate control valve with high sensitivity pilot.

Working conditions

  • Fluid: treated water.
  • Minimum operating pressure: 1,2 bar.
  • Maximum operating pressure: 16 bar. Higher on request.
  • Maximum temperature: 70 °C.

Flow rate control pilot adjustment range

  • The orifice plate assembly is calculated and machined according to the maximum flow rate. An adjustment range of the value is possible according to the regulation flow chart supplied with the valve.

Operating principle

It is operated by a two 2 ways pilot (5), for flow control, with pre-set set and adjustable values, sensing the drop in pressure produced by the orifice plate (13), where a stainless steel disk is inserted inside a flange and connected to the pilot with a sensing line (14) non supplied.


Should the flow exceed the maximum value the differential pressure will increase, and pilot (5) will throttle and limit the flow to direct inlet pressure to the main chamber (10), to generate the head loss required through the seat (12) for the valve (9) to control the flow.

Should the flow remain below the pilot’s set point, the differential pressure across the orifice plate (13) will be less than the pilot’s (5) spring force, therefore the valve will remain fully open.

Pressure in and out of the main chamber (10) is controlled by the regulation device with filter (4), needed for the valve’s response time and accuracy.

Flow Rate Automatic Control Valve - E3114-00 - E4114-00-functioning

Installation layout

The picture shows the recommended lay-out of the valve. The flange orifice (8), calculated and machined according to the project’s requirements, is connected to the valve’s pilot (9).

Sectioning devices (1, 2) and by-pass are very important for maintenance operations, as well as the filter (3) to prevent dirt from reaching the control valve.

Anti-surge combination air valves (6, 7) are recommended, as well as a pressure relief valve, like DRVD (5) to prevent rise in pressure on the main line.

Flow Rate Automatic Control Valve - E3114-00 - E4114-00-installation