Tuyau_Tyton_zmu
ZMU

ZMU pipes DN80 to 300 with TYTON socket

Application
Product family
Pipes

Technical design

Tuyau_Tyton_zmu
80 6.000 C50 4.9 5 98 100.5 84 167.0 16.3 264546
100 6.000 C50 4.9 5 118 120.5 88 188.0 19.8 264547
125 6.000 C50 4.9 5 144 146.5 91 215.0 24.4 266034
150 6.000 C50 5.0 5 170 172.5 94 242.0 29.3 266036
200 6.000 C50 5.4 5 222 224.5 100 295.0 40.5 266038
250 6.000 C50 6.4 5 274 276.5 105 352.0 56.1 177963
300 6.000 C50 7.4 5 326 328.5 110 410.0 74.1 177968

Features

Legend:

  • DN: nominal diameter

  • Lu: laying length, in m

  • Class: pressure class according to EN 545 and ISO 2531

  • e: nominal thickness according to ISO 2531, in mm

  • e1: external thickness of ZMU coating, in mm (cement mortar with acrylic fibers and resin) according to EN15542

  • ØDE: external nominal diameter of the barrel according to EN 545 and ISO 2531, in mm

  • ØDI: internal nominal diameter of the socket, in mm

  • P: nominal depth of the socket, in mm

  • ØB: nominal diameter of the socket, in mm

  • Mass: total mass per metre (including cement coating and socket), determined with the nominal thickness, in kg/m

  • Reference: commercial reference Saint-Gobain PAM

Field of use:

  • For drinking water supply networks

Main characteristics:

  • Joint in alimentary elastomer EPDM (ACS, KTW, WRAS,…)

  • External coating: a layer of zinc-aluminium 85/15 alloy, enriched with copper, with a minimum surface density of 400g/m², applied by spraying molten metal onto the surface of the iron, using an electric arc spray gun, from ZnAl (Cu) alloy wire + a protective layer of Aquacoat (semi-permeable), a water-based blue acrylic of average thickness 80 microns applied using a spray gun + cement mortar ZMU with polymeric additiv and reinforced with PE fibers

  • Internal coating: sulfate resisting blast furnace cement mortar

  • ZMU pipes are in conformity with EN 545

  • ZMU coating in conformity with EN 15542

Type of soils:

ZMU coating can be in contact with nearly all types of soil. Please consider the following matrix based upon resistivity of soils. In case of doubt, please advise.

TI_S_SchemarsistivitZMU_en-001_00001.jpg

Type of water:

Ductile iron pipes with internal coating of sulphate resisting blast furnace cement mortar (SRC) are adapted to convey all types of drinking water in conformity with Directive EU 2020/2184.

In case of other type of water, please refer to below information to check the compatibility with cement mortar.

 

Minimum value

Maximum value

Parameter

pH

CO2 aggressive

Sulphate

Magnesium

Ammonium

Unit

-

mg/l

mg/l

mg/l

mg/l

Value

5,5

15

3000

500

30

Other cement lining also available on request. 

Documents