Tuyau_Tyton_Uni_Vi_zmu
ZMU

ZMU pipes DN80 to 300 with UNIVERSAL TYTON socket

Application
Product family
Pipes

Technical design

Tuyau_Tyton_Uni_Vi_zmu
80 5.970 C100 6.1 5 98 100.5 143.0 158.0 19.1 177867
100 5.970 C100 6.1 5 118 120.5 140.0 188.0 23.3 177821
125 5.970 C64 6.1 5 144 146.5 139.9 203.0 28.6 177865
150 5.970 C64 6.2 5 170 172.5 148.0 230.0 34.4 177797
200 5.970 C64 6.5 5 222 224.5 155.0 290.0 47.0 177805
250 5.970 C50 6.8 5 274 276.5 166.0 350.0 60.9 177768
300 5.970 C50 7.4 5 326 328.5 180.0 408.0 77.6 177781

Features

Legend:

  • DN: nominal diameter

  • Lu: laying length, in m

  • Class: pressure class according to EN 545 and ISO 2531

  • e: nominal thickness according to ISO 2531, in mm

  • e1: external thickness of ZMU coating, in mm (cement mortar with acrylic fibers and resin) according to EN15542

  • ØDE: external nominal diameter of the barrel according to EN 545 and ISO 2531, in mm

  • ØDI: internal nominal diameter of the socket, in mm

  • P: nominal depth of the socket, in mm

  • ØB: nominal diameter of the socket, in mm

  • Mass: total mass per metre (including cement coating and socket), determined with the nominal thickness, in kg/m

  • Reference: commercial reference Saint-Gobain PAM

Field of use:

  • For drinking water supply networks

Main characteristics:

  • Joint in alimentary elastomer EPDM (ACS, KTW, WRAS,…)

  • External coating: a layer of zinc-aluminium 85/15 alloy, enriched with copper, with a minimum surface density of 400g/m², applied by spraying molten metal onto the surface of the iron, using an electric arc spray gun, from ZnAl (Cu) alloy wire + a protective layer of Aquacoat (semi-permeable), a water-based blue acrylic of average thickness 80 microns applied using a spray gun + cement mortar ZMU with polymeric additiv and reinforced with PE fibers

  • Internal coating: sulfate resisting blast furnace cement mortar

  • ZMU pipes are in conformity with EN 545

  • ZMU coating in conformity with EN 15542

Type of soils:

ZMU coating can be in contact with nearly all types of soil. Please consider the following matrix based upon resistivity of soils. In case of doubt, please advise.

TI_S_SchemarsistivitZMU_en-001_00001.jpg

Type of water:

Ductile iron pipes with internal coating of sulphate resisting blast furnace cement mortar (SRC) are adapted to convey all types of drinking water in conformity with Directive EU 2020/2184.

In case of other type of water, please refer to below information to check the compatibility with cement mortar.

 

Minimum value

Maximum value

Parameter

pH

CO2 aggressive

Sulphate

Magnesium

Ammonium

Unit

-

mg/l

mg/l

mg/l

mg/l

Value

5,5

15

3000

500

30

Other cement lining also available on request. 

Documents