html_m3bdd27b8
PI_C9P_VR_BD_rac_storz
PI_C9P_VR_BC_rac_storz
Logo CE
html_m3bdd27b8
PI_C9P_VR_BD_rac_storz
PI_C9P_VR_BC_rac_storz
Logo CE
C9+

Fire hydrant C9+ Traffic DN80-100 - Storz outlets

Application
Product family
Hydrants
  • Operating triangular cap 39mm
  • Bended valve box or straight valve box
  • Automatic drainage function
  • Outlets: 2 Storz lateral outlets and 1 Storz frontal outlet or 1 Storz frontal outlet

Technical design

PI_C9P_VR_BD_rac_storz
PI_C9P_VR_BC_rac_storz
100 Bended box 1x2"½ + 1x2" + 1x4" 1006 2040 643 538 1175 152 100 x 90 76 164247
100 Bended box 1x2"½ + 1x2" + 1x4" 600 1640 643 538 775 152 100 x 90 66 164248
100 Bended box 2x2"½ + 1x4" 1006 2040 643 538 1175 152 100 x 90 76 166704
100 Bended box 2x2"½ + 1x4" 600 1640 643 538 775 152 100 x 90 66 166705
100 Straight box 2x2"½ + 1x4" 1250 2278 643 538 1438 180 200x200 119.5 175991
100 Bended box 2x2" + 1x2"½ 1006 2040 643 538 1175 152 100 x 90 78 183220
80 Bended box 1x2"½ 969 1961 553 1121 123 95 x 80 78.5 206082
100 Straight box 2x2"½ + 1x4" 1500 2528 643 538 1688 180 200 x 200 125 207230
80 Bended box 2x2" + 1x2"½ 969 1961 652 553 1121 123 95 x 80 78 RYA80DCBJB
80 Straight box 2x2" + 1x2"½ 1249 2248 652 553 1408 165 180x180 108 RYA80DQCJB

Features

Field of use

Fire hydrants pillar or underground type are designed, according to applicable standards and regulations, for exclusive use of fire protection and using drinking water or raw water network.


They must be handled and used in strict compliance with the recommendations and best practice by personnel trained with these recommendations.


These devices must be inspected periodically (as required by regulations or recommended instructions) to verify and maintain their proper and safe operation.

Material and coating

Item Designation Material Coating

1

1a -Operating cap

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Dacromet + grey Polyurethane 20 µm

  1c -Upper body Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 Red-brown Epoxy powder 250 µm + red Polyurethane 40 µm
  1f – Lower Body Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 Epoxy powder 250 µm + red Polyurethane 40 µm
  1 g – Screwed box Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 Epoxy powder 250 µm + red Polyurethane 40 µm
  1d-Extension tube Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 Blue Epoxy powder 250 µm
  1e -Valve box Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 Blue Epoxy powder 250 µm
  1b- Cover Polyamide P A 6 Red polyurethane paint

2

Upper and lower bush

Brass type Cu Zn 39 Pb 2EN 12164

 

3

Operating stem

Steel type X20 Cr 13 EN 10088-3

 

4

Operating nut

Brass type Cu Zn 40 Pb 2 EN 12164

 

5

Fixing screw

Steel type CL 8/8

Bichromated zinc

6

Operating rod

Steel type Tu 56 B NF EN 10240

Galvanized

7

Valve

Ductile iron GS EN GJS 400-15 or 500-7 EN 1563

Encapsulated EPDM

8

Outlets

Depending on models

 
9 Operating shaft X20 Cr 13 EN 10088-1  

10

Pin

X20 Cr 13 EN 10088-1
11 Operating spindle (OS) Forged steel C35 - NF EN 10083-1 25 microns black cataphoresis
12

Bolts and nuts

Steel type CL 8/8 Bichromated zinc
13 Breakable traffic clamping shim Ductile iron

250 microns fusion bonded blue epoxy + red polyurethane

Notice NPPI 01 A 

PI_C9P_R_nom