INTEGRAL PH1 PUX pipes DN150 to 2000 with STANDARD socket
Technical design
| 150 | 6.000 | 5.0 | 1.5 | 170 | 173.4 | 100.5 | 242.0 | 20.5 | 40 | TSB15S60VH |
| 200 | 6.000 | 5.1 | 1.5 | 222 | 225.2 | 106.5 | 295.0 | 27.1 | 40 | TSB20S60VH |
| 250 | 6.000 | 5.3 | 1.6 | 274 | 276.8 | 105.5 | 352.0 | 35.5 | 38 | TSB25S60VH |
| 300 | 6.000 | 5.6 | 1.6 | 326 | 328.8 | 107.5 | 409.2 | 44.6 | 35 | TSB30S60VH |
| 350 | 6.000 | 6.0 | 1.6 | 378 | 380.9 | 110.5 | 444.5 | 55.2 | 32 | TSB35S60VH |
| 400 | 6.000 | 6.3 | 1.6 | 429 | 431.9 | 112.5 | 494.6 | 65.4 | 30 | TSB40S60VH |
| 450 | 6.000 | 6.7 | 1.6 | 480 | 483.0 | 115.5 | 546.5 | 78.1 | 29 | TSB45S60VH |
| 500 | 6.000 | 7.0 | 1.6 | 532 | 535.0 | 117.5 | 600.9 | 90.5 | 28 | TSB50S60VH |
| 600 | 6.000 | 7.7 | 1.6 | 635 | 638.1 | 132.5 | 712.0 | 118.8 | 26 | TSB60S60VH |
| 700 | 6.960 | 9.6 | 1.8 | 738 | 741.7 | 192.0 | 821.9 | 172.3 | 29 | TSB70E70VH |
| 800 | 6.950 | 10.4 | 1.8 | 842 | 845.8 | 197.0 | 935.6 | 213.1 | 28 | TSB80E70VH |
| 900 | 6.950 | 11.2 | 1.8 | 945 | 948.9 | 200.0 | 1043.4 | 257.2 | 27 | TSB90E70VH |
| 1000 | 6.960 | 12.0 | 1.8 | 1048 | 1052.0 | 203.0 | 1152.4 | 309.63 | 26 | TSC10E69VH |
| 1100 | 8.190 | 14.4 | 2.2 | 1152 | 1155.1 | 225.0 | 1300.0 | 440 | 29 | TSC11N80VH |
| 1200 | 8.190 | 15.3 | 2.2 | 1255 | 1260.0 | 235.0 | 1373.7 | 463.8 | 29 | TSC12N80VH |
| 1400 | 8.170 | 17.1 | 2.2 | 1462 | 1467.9 | 245 | 1592.1 | 605.01 | 28 | * |
| 1500 | 8.160 | 18.0 | 2.2 | 1565 | 1571.1 | 265 | 1709.8 | 684.83 | 27 | * |
| 1600 | 8.160 | 18.9 | 2.5 | 1668 | 1674.2 | 265 | 1815.9 | 769.06 | 27 | * |
| 1800 | 8.150 | 20.7 | 2.5 | 1875 | 1881.5 | 275 | 2032.2 | 943.16 | 27 | * |
| 2000 | 8.130 | 22.5 | 2.5 | 2082 | 2088.8 | 290 | 2259.0 | 1138.95 | 26 | * |
Features
Legend:
-
DN : nominal diameter
-
Lu : laying length, in m
-
e: thickness according to EN598 + A1 – August 2009, in mm
-
er: thickness of the polyurethane, according to NF EN 15655 – March 2009, in mm
-
ØDE : external nominal diameter of the barrel according to EN598 + A1 – August 2009, in mm
-
ØDI : internal nominal diameter of the socket, in mm
-
P : nominal depth of the socket, in mm
-
ØB : nominal diameter of the socket, in mm
-
Mass : total mass per meter (including polyurethane coating and socket), determined with the nominal thickness, in kg/m
-
Reference : commercial reference Saint-Gobain PAM
Field of use:
-
Separate sewer system and combined sewer system
-
Application: gravity flow and rising main sewerage systems
-
Type of effluent: domestic wastewater and rainwater
-
For industrial effluents after study of our technical department
-
Perfectly watertight
-
For effluents between pH1 and pH13
-
Extremely corrosive soils
-
Resistivity of the soils:
Main characteristics:
-
External and internal coating: polyurethane
-
Spigot and socket coating: reinforced red epoxy paint 300 microns (mini average)
-
Standard Gasket in Nitrile
-
EN 598 / EN 15655 / EN 15189 / CE Marking
-
Declaration of performances DoP-INTEGRAL005EN
- Designed in accordance with applicable regulations:
- NF EN 476: general stipulations regarding components used in systems
- NF EN 752: design of sewerage projects
- NF EN 1610: acceptance of structures