Upstream Pressure Support Hydrovalve with remote Electric Control - E3116-31 / E4116-31
The automatic valve supports the upstream pressure regardless of flow rate variations; the calibration value is adjustable.
With the aid of a solenoid valve, it is also possible to open or close by means of a control unit or remote impulses.
If the upstream pressure should fall below the calibration value, the valve will move to the fully closed position, ensuring operation even in static conditions.
Flange drilling according to EN 1092/2, different on request.
Certification and testing according to EN 1074.
Technical design
| E3116-31 | 80 | 10 16 | 31 | E36A8016P31 |
| E3116-31 | 100 | 10 16 | 36 | E36B1016P31 |
| E3116-31 | 125 | 10 16 | 51 | E36B1216P31 |
| E3116-31 | 150 | 10 16 | 58 | E36B1516P31 |
| E3116-31 | 200 | 10 | 102 | E36B2010P31 |
| E3116-31 | 200 | 16 | 102 | E36B2016P31 |
| E3116-31 | 250 | 10 | 176 | E36B2510P31 |
| E3116-31 | 250 | 16 | 176 | E36B2516P31 |
| E3116-31 | 300 | 10 | 293 | E36B3010P31 |
| E3116-31 | 300 | 16 | 293 | E36B3016P31 |
| E3116-31 | 400 | 10 | 500 | E36B4010P31 |
| E3116-31 | 400 | 16 | 500 | E36B4016P31 |
| E3116-31 | 500 | 10 | 862 | E36B5010P31 |
| E3116-31 | 500 | 16 | 862 | E36B5016P31 |
| E3116-31 | 600 | 10 | 1002 | E36B6010P31 |
| E3116-31 | 600 | 16 | 1002 | E36B6016P31 |
| E4116-31 | 40/50 | 10 16 | 25 | E46A5016P31 |
| E4116-31 | 65 | 10 16 | 25 | E46A6516P31 |
| E4116-31 | 80 | 10 16 | 30 | E46A8016P31 |
| E4116-31 | 100 | 10 16 | 43 | E46B1016P31 |
| E4116-31 | 150 | 10 16 | 89 | E46B1516P31 |
| E4116-31 | 200 | 10 | 142 | E46B2010P31 |
| E4116-31 | 200 | 16 | 142 | E46B2016P31 |
| E4116-31 | 250 | 10 | 253 | E46B2510P31 |
| E4116-31 | 250 | 16 | 253 | E46B2516P31 |
| E4116-31 | 300 | 10 | 425 | E46B3010P31 |
| E4116-31 | 300 | 16 | 425 | E46B3016P31 |
| E4116-31 | 400 | 10 | 784 | E46B4010P31 |
| E4116-31 | 400 | 16 | 784 | E46B4016P31 |
| E4116-31 | 600 | 10 | 2250 | E46B6010P31 |
| E4116-31 | 600 | 16 | 2250 | E46B6016P31 |
Features
Applications
- On the supply lines of the tanks to regulate, connected to an electronic float probe, flow rate and level.
- In gravity pipelines to ensure supply to users located in the highest areas together with the possibility of closing and opening in response to control or alarm signals.
Accessories
- Open-close indicator.
- Manometers.
- Self-cleaning high capacity filter.
- Limiter of opening manual
Directions for use
- Inlet and outlet pressure, flow rate and application are required for cavitation sizing and analysis.
- In the support function a distance of 3 diameters upstream of the valve is recommended for best operation
Optional configurations
- Upstream pressure sustaining valve with solenoid control valve and anti-backflow system.
- Upstream pressure relief valve with quick-acting solenoid and pilot control valve.
- Upstream pressure sustaining valve with high sensitivity solenoid and pilot control valve.
Operating conditions
- Fluid: treated water.
- Minimum pressure: 0,7 bar.
- Maximum pressure: 16 bar. Higher on request.
- Maximum temperature: 70 °C.
Solenoid valve data
- Voltage: 24V DC, 24V/50Hz, 230V/50Hz. Other voltage on request.
- Electrical consumption: inrush AC (VA) 24, hold AC (VA) 17 (8 W), DC hot/ cold coil 8/9 W.
How it works
The automatic valve is controlled by an adjustable two-way pilot (5) which receives, through the regulation unit (4), the upstream pressure value.
When the latter rises above the set-point, the pilot (5) opens; the pressure in the valve chamber (10) consequently decreases, causing the shutter (11) to rise.
When the pressure is lower than the set value, the pilot reduces the degree of opening by modulating; the pressure in the chamber (10) increases and the shutter (11) descends towards the seat (12), reducing or interrupting the flow through the main valve.
Furthermore, a solenoid (14), which acts on a two-way auxiliary valve (13), interrupts the flow of the circuit, causing the main valve to close in response to remote impulses. Upon request, it is also possible to force the total opening of the hydrovalve.
Installation diagram
In the installation diagram of the valve, connected to an electronic control unit (7) which sends pulses to the circuit solenoid, shut-off devices (1, 2) and bypass allow maintenance,
And a filter (3) holds back possible impurity. There valve Of support to action live (4), reliable even after long periods of inactivity, represents the best solution for the bypass. The insertion of anti-water hammer vents (5, 6) upstream and downstream is also recommended.