Fire hydrant C9+ Traffic DN100 - BS outlets
- Operating square cap 30x30mm
- Bended valve box
- Automatic drainage function
- Outlets: 2 lateral outlets BS336 and 1 frontal outlet BS336
Technical design
| 100 | Bended box | 2x BS336 2"½ DN 65 + 1x 4" DN100 | 1006 | 2050 | 643 | 538 | 1175 | 152 | 100 x 90 | 83 | 182101 |
| 100 | Straight box | 2x BS336 2"½ + 1x BS336 4" | 1250 | 2278 | 643 | 538 | 1438 | 180 | 200 x 200 | 101 | * |
Features
Field of use
Fire hydrants pillar or underground type are designed, according to applicable standards and regulations, for exclusive use of fire protection and using drinking water or raw water network.
They must be handled and used in strict compliance with the recommendations and best practice by personnel trained with these recommendations.
These devices must be inspected periodically (as required by regulations or recommended instructions) to verify and maintain their proper and safe operation.
Material and coating
| Item | Designation | Material | Coating |
|---|---|---|---|
|
1 |
1a -Operating cap |
Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 |
Dacromet + grey Polyurethane 20 µm |
| 1c -Upper body | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Red-brown Epoxy powder 250 µm + red Polyurethane 40 µm | |
| 1f – Lower Body | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Epoxy powder 250 µm + red Polyurethane 40 µm | |
| 1 g – Screwed box | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Epoxy powder 250 µm + red Polyurethane 40 µm | |
| 1d-Extension tube | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Blue Epoxy powder 250 µm | |
| 1e -Valve box | Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 | Blue Epoxy powder 250 µm | |
| 1b- Cover | Polyamide P A 6 | Red polyurethane paint | |
|
2 |
Upper and lower bush |
Brass type Cu Zn 39 Pb 2EN 12164 |
|
|
3 |
Operating stem |
Steel type X20 Cr 13 EN 10088-3 |
|
|
4 |
Operating nut |
Brass type Cu Zn 40 Pb 2 EN 12164 |
|
|
5 |
Fixing screw |
Steel type CL 8/8 |
Bichromated zinc |
|
6 |
Operating rod |
Steel type Tu 56 B NF EN 10240 |
Galvanized |
|
7 |
Valve |
Ductile iron GS EN GJS 400-15 or 500-7 EN 1563 |
Encapsulated EPDM |
|
8 |
Outlets |
Depending on models |
|
| 9 | Operating shaft | X20 Cr 13 EN 10088-1 | |
|
10 |
Pin |
X20 Cr 13 EN 10088-1 | |
| 11 | Operating spindle | (OS) Forged steel C35 - NF EN 10083-1 | 25 microns black cataphoresis |
| 12 |
Bolts and nuts |
Steel type CL 8/8 | Bichromated zinc |
| 13 | Breakable traffic clamping shim | Ductile iron |
250 microns fusion bonded blue epoxy + red polyurethane |
Notice NPPI 01 A
Mechanical characteristics
- According to NF EN 14384/CN
- PFA 16 bars (hydraulics test: According to ISO 5208)
- Opening-closing torque bellow 80 Nm
- Maximum strength torque above 300 Nm
- Resistance to 1000 cycles opening/closing
- Number of turns to close: 13
- Nominal flow rate 60m3/h for headloss 1 m. water column
- Flow curve for PI C9+ DN100 (with headloss 1 bar:10 m. water column) according to the numbers of turns opening
Installation
See drawing:
- Surface boxes
- Gate valve Euro 20
- S height adjustment bends
- Concrete block
- Drain orificeAnchorage concrete block at ground level 50 x 50 x thickness 15cm
Installation DN100
Hc 1000 : 500 to 600 maxi
Hc 1250 : 500 to 600 maxi
- Close the pillar
- Open one outlet
- Flush the system at high flow
- Check that the pillar is empty
- Close the outlet